Brahma NDM11PR 37505004 Burner Management System

Brahma
  1. Burner Parts
  2. Automatic burner control units

Description

The Brahma NDM11PR 37505004 combustion manager ensures reliable operation and control of atmospheric gas and liquid fuel burners with intermittent operation. It is characterized by a high level of safety and ease of operation. 

More about the model

The Brahma NDM burner automatic is based on microprocessor technology. It is supplied with an ignition transformer and an anti-interference filter. An ionization electrode or FD photodetector is used for continuous flame control. When flame loss is detected, the automation immediately stops fuel supply, blocking the burner operation. Exiting the protective shutdown state is performed using a reset button. 

The electronic circuit and components are reliably protected by a housing made of impact-resistant plastic. Dust and moisture protection is absent.

Main parameters:

  • operation from a 220-240 V, 50/60 Hz power grid;
  • intermittent cycle, controlled restart for self-checking of components;
  • pre-ventilation duration: 30 sec.;
  • ionization flame control or using an FD sensor; 
  • indication of current status and errors;
  • manual release from lock;
  • possibility of connecting an external reset device;
  • fast response to threats, locking within < 1 sec.;
  • operating temperatures: -20...+70 °C;
  • ignition device, filter from electromagnetic interference;
  • degree of protection against dust/moisture impact according to IP 00 standard;
  • compact design, simple installation and connection.

Application

Brahma NDM burner automatics are used to complete atmospheric progressive burners burning gas or liquid fuel. 


Characteristics

Safety time (ts): 4 sPre-ventilation time (tv/tp): 30 sDegree of protection: IP00Operating ambient temperature: from -20 to 70 °CBurning method: atmosphericOperating mode: intermittentPresence of a plinth: noFuel type: gaseous, liquid-fueledBurner type: progressiveVoltage: 220 V - 220 V