Dungs FLW 10 IR V2.1 flame sensor

Dungs255216
  1. Burner Parts
  2. Flame sensors

Description

The Dungs FLW 10 IR V 2.1 flame sensor, art: 255216, has high spectral sensitivity. Equipped with an IR sensor to register radiation from the blue flame of the burner. Suitable for systems with an intermittent cycle.

Parameters and features:

  • registration of the infrared spectrum of the flame;
  • high sensitivity element;
  • frontal measurement;
  • operating voltage: 220-230 V, -15%, +10%, frequency 50/60 Hz;
  • operating temperatures (ambient air): from -20 to +60 °C;
  • mounting variability;
  • housing protection against dust and moisture according to IP 41 standard;
  • length of the instrument body – 115 mm;
  • for combustion systems with a repeated-short-term cycle.

More about the model

The infrared sensor determines the flicker frequency of the flame. Stray light from fluorescent lamps and other objects is not registered as a flame. At the same time, when installing the device, direct visibility of the transformer spark and external lighting should be excluded. The sensor is installed in the system in any convenient position for detection. A flange connection or holder is used for mounting.

Characteristics

Manufacturer Part Number: 255216Casing length: 115 mmOperating ambient temperature: from -15 to 60 °CDegree of protection: IP41Class of sensitivity: highDirection of illumination: frontalFlame sensor type: infrared