The Siemens LMO24.111C2 burner automation unit can replace Siemens LOA24.171B27, LOA26.171B27*, LOA36.171B27* burner automation units, but it is necessary to follow the instructions provided in the product's technical documentation.

The Siemens LMO 24.111C2 burner automation unit is an electronic device for the safe start-up, monitoring and control of single-stage and two-stage liquid fuel burners with intermittent operation and a capacity of less than 30 kg/h. The device has been tested and certified in accordance with European standards. Supplied without a base.

Operating and technical parameters

  • Power supply connection: 220-230 V, 50/60 Hz.
  • Power consumption: approximately 12 VA.
  • Working environment: liquid fuel.
  • Operating mode: intermittent.
  • Operating temperature: -5ºC...+60ºC.
  • Purge duration: 16 seconds.
  • Safety time: 10 seconds.
  • Time before ignition: 15 seconds.

Device and комплектация

The burner manager has a compact, detachable design that attaches to the base with a latch. The body material is heat-resistant, durable plastic. Protection of electrical components according to IP 40 standard is provided by installation.
The device includes an electronic flame signal amplifier, relays, a microcontroller controlling the command sequence.
A convenient button with a built-in multi-colored indicator is located on the front panel for locking/unlocking the device. A flashing lamp indicates emergency situations. A three-color LED and a special well-thought-out coding system make it easy to identify the causes of failures. The button has a socket for an interface adapter or extension cable connection.

Flame memory control

Siemens provides flame combustion control, working in conjunction with a photoresistive QRB sensor (yellow flame) and a blue flame QRC sensor (oxidizing flame).

Functionality and features:

  • Remote reset (restart) of the automation is possible;
  • Instant (less than 1 second) shut-off of fuel supply when the lock is activated;
  • Recognition of low voltage in the network, shutdown when the minimum limit (165 Volts) is reached with subsequent automatic start-up when network parameters are restored;
  • Availability of a shunting contact for the heating element;
  • Fuel heater timing control function;
  • Accurate execution of program commands thanks to digital signal processing;
  • Controlled automatic restart of the automation every 24 hours of operation;
  • Limited number of repetitions (no more than 3 starts) within a single controlled start;
  • Convenient system for reporting current operation and emergency failures using a three-color lamp or software.

Before purchasing the Siemens LMO24.111C2 burner automation unit, we recommend that you consult our specialist. We will advise you on the optimal equipment option at an affordable price, taking into account the specifics of your project.

.

Characteristics

Safety time (ts): 10 sPreignition time (tvz): 15 sPre-ventilation time (tv/tp): 16 sOperating ambient temperature: from -5 to 60 °CBurning method: turbochargedOperating mode: intermittentRemote restart capability: yesPresence of a plinth: noDegree of protection: IP40Fuel type: liquid-fueledBurner type: two-stageVoltage: 220 V