Siemens LOA24.571C27 burner control system

Siemens
  1. Burner Parts
  2. Automatic burner control units

Description

The Siemens LOA24.571C27 burner control is based on microprocessor technology, which contributes to the accurate execution of the specified command sequence. It automates the start-up, combustion stages, flame monitoring, and safe shutdown of the system in case of malfunctions and failures. Supports intermittent operation. Initiates a periodic restart every 24 hours for self-diagnosis of malfunctions. Using color indication, it informs the user about operating statuses and failures.

Main characteristics and functions:

  • control of forced-draft two-stage burners burning liquid fuel;
  • power supply from 220-240 V, 50-60 Hz network;
  • intermittent mode, periodic restart every 24 hours for self-diagnosis;
  • flame monitoring using a photoresistor QRB or QRC sensor;
  • fast response to flame loss;
  • dust and moisture protection level of electrical components: IP40;
  • voltage surge protection system (safe shutdown, restart);
  • de-energization of fuel valves, burner motor and ignition system in case of lock-out for 1 sec.;
  • color indication for tracking the operating stage, informing about failures;
  • possibility of remote lock-out reset;
  • connection contact for fuel heater;
  • housing made of impact-resistant heat-resistant plastic;
  • ambient air temperatures: -5...+60 °C;
  • restart button to exit lock-out, activate diagnostic mode;
  • supplied with cables for electrical connection, without base.

Burner controls comply with European standard EN230 and CE requirements regarding electromagnetic compatibility. For more information, please contact our consultants.

Characteristics

Safety time (ts): 10 sOperating ambient temperature: from -20 to 60 °CBurning method: turbochargedOperating mode: intermittentCable set for connection: yesRemote restart capability: yesPresence of a plinth: noBurner type: two-stageDegree of protection: IP40Fuel type: liquid-fueledVoltage: 220 V