Suntec AP2 75 C 9562 4P 0700 Burner Pump

Suntec
  1. Burner Parts
  2. Burner pumps

Characteristics

Nozzle outlet: ⅛ inchSolenoid valve voltage: 220-240 or 110-120 or 24 VBy-pass plug: It is installed in the return line for a two-pipe system and is removed with a hexagonal wrench withVacuum gauge port: ⅛ inchPressure gauge port: ⅛ inchPump series: AP: 2-stage model (one nozzle line and two pressure modes), no shut-off functionReturn pressure: 2 barTorque: 0.14 N·mFactory installations for high pressure: 22 barFactory settings for low pressure: 9 barMaximum rotation speed: 3,600 rpmMaximum pressure of the solenoid valve: 25 barNominal rotation speed: 2,850 rpmSolenoid valve consumption: 9 WStrainer: Open area: 20 cm²Strainer: Opening size: 150 µmOperating viscosity: from 2 to 12 mm²/sValve function: pressure regulation without locking functionInstalling the bypass plug: P: bypass plug installed in return line for two-pipe systemModel type: 2-stage with electromagnetic valveDirection of rotation (looking at the drive shaft): C: counterclockwise rotation / nozzle on the leftOil temperature: from 0 to 60 °C in the pumpShaft design: two cavitiesSuction and return line: ¼ inch NPTF (taper thread)Nozzle pressure range: from 8 to 25 barShaft diameter: 8 mmInlet pressure: 2 barSuction height: 0.45 bars max. vacuum to prevent air separation from oilType of pumped liquid: dieselInstallation method: sleeve ⌀32 mmDegree of protection: IP54