Characteristics
Performance at 11 bar pressure and 5 cSt viscosity: 80 l/hType of pumped liquid: diesel, biodiesel fuel blend B10Installing the bypass plug: P: bypass plug installed in return line for two-pipe systemPump series: AS: pressure regulation and bypass solenoid valvePressure gauge port: ⅛ inchReturn pressure: 2 barTorque: 0.12 N·mMaximum rotation speed: 3,600 rpmMaximum pressure of the solenoid valve: 25 barNominal rotation speed: 2,850 rpmSolenoid valve consumption: 9 WStrainer: Open area: 6 cm²Strainer: Opening size: 150 µmVacuum gauge port: ⅛ inchOperating viscosity: from 2 to 12 mm²/sValve function: pressure regulating and cut-offModel type: 1 stage with electromagnetic valveBy-pass plug: It is installed in the return line for a two-pipe system and is removed with a hexagonal wrench withOil temperature: from 0 to 60 °C in the pumpPerformance for stage 2 at 11 bar and 5 cSt viscosity: 80 l/hSolenoid valve voltage: 220-240V~, 50-60HzShaft design: one cavityFactory pressure setting: 10 barDirection of rotation (looking at the drive shaft): A: clockwise rotation / nozzle on the rightNozzle pressure range: from 10 to 15 barShaft diameter: 8 mmInlet pressure: 2 barSuction height: 0.45 bars max. vacuum to prevent air separation from oilSuction and return line: ¼ inch NPTF (taper thread)Nozzle outlet: ⅛ inchDegree of protection: IP54Installation method: flange ⌀54 mm